Summary

The following three verification results are presented regarding the expansion of polymer matrix composite (hereinafter PMC) conductor applications in Japan.

1. Heat Resistance Characteristics: The compatibility of PMC as the core and ZTAL (TypeAT3) as outer layers was evaluated. The results of tensile strength tests at various high temperatures confirmed that the combination of PMC and ZTAL is feasible and that the cable possesses a high current-carrying capacity.

2. Vibration Characteristics: The vibration characteristics due to galloping and ice shedding of

PMC conductor were evaluated using formulas commonly used in Japan. Although PMC conductor tended to have slightly larger sleet jump height, even in the most severe case of 100% simultaneous ice shedding, the required vertical phase-to-phase clearance was maintained. This result confirms that the applicable span length of PMC conductor is equivalent to that of conventional conductors and no additional countermeasures are necessary. In the galloping study, as long as the span length exceeded a certain level, the vibration amplitude of PMC conductor was smaller than that of conventional conductors. Therefore, it is confirmed that no special countermeasures are required.

3. DC Arc Test: The DC arc test results confirmed that even with the amount of electric charge that melted all strands of a conventional ground wire, only the aluminum melted, while the

PMC core remained undamaged. It was determined that PMC conductor can be safely used as an overhead ground wire.

Additional informations

Publication type Session Materials
Reference B2_10832_2026
Publication year
Publisher CIGRE
Country Japan
Study committees
File size 1 MB
Price for non member 30 €
Price for member 30 €

Authors

YAMAKI Takuo - Kitanihon electric cable Japan; SUDO Naohiko - Tohoku Electric Power Network Japan; FUJII Kento - Tohoku Electric Power Network Japan; SHIRAISHI Tomonori - TEPCO Power Grid Japan; NARA Kiyonobu - Kitanihon electric cable Japan; SUZUKI Motoki - Tokyo Rope International Japan

Keywords

Advanced Conductor, Arc test, Galloping, HTLS, Swinging

Verification for expanding the application of PMC conductor