Summary

Lightning strikes terminating in the vicinity of a cable route may result in high electric field stress across the cable sheath insulation, potentially leading to puncture of the sheath. The present report summarizes findings from a study on protection of buried HVDC cables by bare copper wires. In addition to evaluation of stresses on the HVDC cable sheath insulation, stresses on crossing third-party cables are also considered. Based on results of 3D FEM simulations of electric field stresses, it is concluded that the risk of damage to crossing cables is low.

Additional informations

Publication type Session Materials
Reference B1_11368_2026
Publication year
Publisher CIGRE
Country Sweden
Study committees
File size 750 KB
Price for non member 30 €
Price for member 30 €

Authors

SIDENVALL Peter - I2G; DERNFALK Andreas - I2G; JEROENSE Marc - MarCable-consulting Sweden

Stresses on crossing third-party assets due to lighting strikes along underground HVDC cable rout